A ring final circuit (commonly called a "ring main") is the standard method of wiring socket outlets in UK domestic installations. BS 7671 defines it simply: a final circuit arranged in the form of a ring and connected to a single point of supply. The cable forms a complete loop — starting at the consumer unit, passing through each socket outlet in turn, and returning to the consumer unit. The line, neutral and CPC conductors must all form continuous rings.
The arrangement is set out in BS 7671:2018+A4:2026 Regulation 433.1.204. Accessories to BS 1363 may be supplied through a ring final circuit, with or without unfused spurs, protected by a 30 A or 32 A protective device — so a 32 A MCB is the usual choice, but not the only compliant one. The circuit is wired in copper with line and neutral conductors of at least 2.5mm² (1.5mm² for two-core mineral insulated cable to BS EN 60702-1). Such circuits are deemed to satisfy the overload rules of Regulation 433.1.1 if the current-carrying capacity of the cable is not less than 20 A and the load current in any part of the circuit is unlikely to exceed that capacity for long periods.
Two further points do the real work in fault finding. Regulation 543.2.9 requires the CPC of every ring final circuit to be run in the form of a ring with both ends connected to the earthing terminal at the origin — the only exception being where the CPC is formed by a metal covering or enclosure containing all the conductors of the ring, such as steel conduit. And Regulation 643.2.1(b) requires that, in the case of ring final circuits, the continuity of the live conductors is verified by a measurement of resistance. That is the regulation behind the three-step test, and it is why ring testing is part of every EICR.
This design works well when the ring is intact. When the ring has a fault — an open ring, a bridge, or a borrowed conductor — the current distribution changes and sections of cable can carry more current than they are rated for.