Regulation 722.411.4.1 is the most significant requirement in Section 722 and the one that causes the most confusion. It restricts the use of PME (TN-C-S) earthing for EV charging installations.
The PME Problem
Most UK domestic supplies are TN-C-S (PME). The combined PEN conductor in the DNO supply cable serves as both neutral and earth. If the PEN conductor breaks (open PEN fault), all metalwork connected to the PME earth rises to a dangerous voltage relative to true earth. Inside the building, the main bonding creates an equipotential zone — so the person touching a radiator and a metal socket faceplate is protected because both are at the same potential.
An EV charger installed outside the building (on a driveway, in a car port, or on an external wall) is outside this equipotential zone. A person standing on the ground while touching the vehicle being charged could receive a shock from the voltage difference between the PME earth and true earth. This is why Regulation 722.411.4.1 requires additional earthing measures.
Under A4:2026, the structure of Regulation 722.411.4.1 changed. Indent (a) was deleted (Reg 722.826.3.201 records this deletion). A new indent (iv) was added as an alternative solution. The current A4:2026 regulation provides methods (b), (c), (d), (e), and the newly added (iv) — a PME earthing facility must not be used directly for an outdoor EV charging point protective conductor contact unless one of these alternatives is applied. The Annex to Part 722 has also been redrafted, with updated guidance on method (c) (the voltage-monitoring disconnect device). Always apply the A4:2026 text; earlier editions with indent (a) are superseded.
The regulation requires that where the EV charger is connected to a PME supply and the charging point is accessible from outside the main equipotential zone, an earth electrode must be provided, or one of the other permitted arrangements must be used.