Most temporary installations end up on TT, because BS 7671 restricts PME on exactly the kind of work temporary installations involve. That decision then drives everything else: on TT, fault protection is by RCD, so the electrode resistance and the RCD rating have to satisfy Regulation 411.5.3 together.
TT fault protection: the numbers
Regulation 411.5.3 sets two conditions. Disconnection must be within the time required by Regulation 411.3.2.2 or 411.3.2.4, and RA × IΔn must not exceed 50 V. The requirement is met if the earth fault loop impedance meets Table 41.5.
| RCD rated residual operating current (IΔn) | Maximum Zs — Table 41.5, U0 230 V |
|---|
| 30 mA | 1667 Ω |
| 100 mA | 500 Ω |
| 300 mA | 167 Ω |
| 500 mA | 100 Ω |
The 1667 Ω and 500 Ω figures carry a note in Table 41.5: the resistance of the installation earth electrode should be as low as practicable, and a value exceeding 200 Ω may not be stable (see Reg 542.2.4). That 200 Ω is a stability caution, not the compliance limit — the compliance limits are the ones tabulated above. On poor ground, drive more electrodes.
Maximum disconnection times
Table 41.1 applies to final circuits rated up to 63 A with one or more socket-outlets, and up to 32 A supplying only fixed connected equipment (Reg 411.3.2.2). Figures below are for AC at U0 of 230 V.
| System | Final circuit within Reg 411.3.2.2 | Distribution circuit |
|---|
| TT | 0.2 s | 1 s (Reg 411.3.2.4) |
| TN | 0.4 s | 5 s (Reg 411.3.2.3) |
Where disconnection on a TT system is achieved by an overcurrent protective device and the protective equipotential bonding is connected to all extraneous-conductive-parts in accordance with Regulation 411.3.1.2, the TN times may be used instead.
Earthing systems for temporary supplies
| System | Source | Suitability for temporary work |
|---|
| TT | Mains or generator with an earth electrode | The usual answer outdoors and on sites. Fault protection relies on RCDs; electrode resistance must be measured (Reg 643.7.2) and satisfy Reg 411.5.3. |
| TN-S | DNO TN-S, or a generator with an earthed star point and a separate protective conductor | Acceptable where a sound, dedicated protective conductor runs all the way back to the source. |
| TN-C-S (PME) | DNO combined PEN | Shall not be used on construction and demolition sites unless every extraneous-conductive-part is reliably connected to the main earthing terminal per Reg 411.3.1.2 (Reg 704.411.3.1). At exhibitions and shows, permitted outside a building only under continuous supervision by a skilled or instructed person, with the means of earthing confirmed before connection (Reg 711.411.4). |
| IT | Unearthed generator | Runs on through a first fault, but needs an insulation monitoring device giving audible and visual signals (Reg 538.1) so the first fault is cleared before a second occurs. |
Where a generating set provides a switched alternative to the public supply, fault protection shall not rely on the connection to the earthed point of the public distribution system — a suitable means of earthing must be provided (Reg 551.4.3.2.1).
Bonding conductor sizes
- Main protective bonding, no PME (Reg 544.1.1). Not less than half the cross-sectional area required for the earthing conductor of the installation, at least 6 mm², and need not exceed 25 mm² in copper or equivalent conductance in another metal.
- Main protective bonding where PME conditions apply (Table 54.8). Selected against the PEN conductor of the supply: 10 mm² for a PEN of 35 mm² or less, 16 mm² over 35 up to 50 mm², 25 mm² over 50 up to 95 mm², 35 mm² over 95 up to 150 mm², and 50 mm² above 150 mm². It is not a flat 10 mm². Where there is more than one source to which PME conditions apply, size against the largest PEN conductor.
- Supplementary bonding (Reg 544.2). Between two exposed-conductive-parts, conductance not less than the smaller protective conductor (Reg 544.2.1). Between an exposed-conductive-part and an extraneous-conductive-part, not less than half the protective conductor connected to the exposed-conductive-part (Reg 544.2.2). Between two extraneous-conductive-parts, not less than 2.5 mm² (Reg 544.2.3). In every case, where mechanical protection is not provided the minimum is 4 mm².
- What to bond. Extraneous-conductive-parts — metallic structures, scaffolding, staging and trusses, metallic services — connected to the main earthing terminal. At exhibitions, structural metallic parts accessible from within the stand, vehicle, wagon, caravan or container shall be connected through the main protective bonding conductors to the main earthing terminal within the unit (Reg 711.411.3.1.2).
The earthing arrangement must be shown on the single-line diagram and verified by testing before the installation is energised.