TECHNICAL GUIDE

Temporary Installations: BS 7909, Events, and Construction Sites

Temporary electrical installations demand the same rigour as permanent ones — and often more. From construction site supplies to festival power systems, this guide covers supply design, earthing, RCD protection, testing, and the documentation that proves compliance.

Free for 7 days · No charge until day 8 · Cancel anytime · Used by 1,000+ UK electricians

12 min readUpdated 2026-06-10Andrew Moore, Founder of Elec-Mate

Written and reviewed by Andrew Moore, founder of Elec-Mate, against BS 7671:2018+A4:2026, IET Guidance Note 3 and the IET On-Site Guide.

ShareXinW
Follow

What is BS 7909 and how does it relate to BS 7671?

BS 7909 is the UK Code of Practice for temporary electrical systems for entertainment and related purposes — outdoor events, concerts, festivals, exhibitions and temporary structures. It supplements BS 7671 (the IET Wiring Regulations) rather than replacing it: every temporary installation must still meet BS 7671 as the baseline. Temporary installations on construction and demolition sites are instead covered directly by BS 7671 Section 704.

Section 704 mandates that a PME (TN-C-S) earthing facility shall not be used on a construction site unless all extraneous-conductive-parts are reliably bonded (Reg 704.411.3.1), and that socket-outlets and hand-held equipment up to 32 A are protected by reduced low voltage, automatic disconnection with a 30 mA RCD, electrical separation or SELV/PELV (Reg 704.410.3.10).

1,000+

UK electricians

“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”

Daniel Palmer — DP Electrical

Key Takeaways

  • 1BS 7909 is the Code of Practice for temporary electrical systems for entertainment and related purposes — it supplements BS 7671 with requirements specific to temporary installations.
  • 2Temporary installations must have an effective earthing system, appropriate RCD protection (30mA for socket outlets), and be designed to withstand the environmental conditions on site.
  • 3All temporary installations must be inspected and tested before first use and at regular intervals thereafter — typically every 3 months on construction sites.
  • 4Comprehensive documentation is required including single-line diagrams, test certificates, risk assessments, and method statements for the installation.
  • 5Elec-Mate generates electrical installation certificates, risk assessments, and RAMS documents for temporary installations — saving hours of paperwork per project.
  • 6RCD type selection matters: Type A covers pulsating DC; Type F covers composite/mixed-frequency loads (variable-speed drives); Type B covers smooth DC components — Type AC (BS 7671 Reg 531.3.3) may now only serve fixed equipment where the load contains no DC components, so it cannot be the default on modern loads.
  • 7Section 704 does not apply to administrative locations on construction sites (offices, canteens, welfare facilities) — those areas are subject to the general requirements of BS 7671 only (Reg 704.1.1).
  • 8On construction and demolition sites a PME (TN-C-S) earthing facility must not be used unless every extraneous-conductive-part is reliably bonded to the main earthing terminal (BS 7671 Reg 704.411.3.1) — in practice TT with an earth electrode is the default.
01 · Technical Guide

What Does BS 7909 Cover?

BS 7909 is the British Standard Code of Practice for the design and installation of temporary electrical systems for entertainment and related purposes. It was developed to address the specific requirements of temporary electrical installations that go beyond what BS 7671 covers for permanent installations.

  • Entertainment and events: Concerts, festivals, theatres, outdoor shows, exhibitions, conferences, and any temporary venue where electrical systems are installed for a limited period.
  • Temporary structures: Marquees, temporary stages, grandstands, hospitality areas, and any structure erected for a temporary purpose that requires an electrical supply.
  • Construction sites: While BS 7671 Section 704 specifically covers construction and demolition site installations, the principles in BS 7909 regarding temporary supply design, environmental protection, and cable management are also applicable.
  • Generator-supplied installations: BS 7909 provides detailed guidance on using generators as supply sources, including earthing arrangements, voltage regulation, and fault protection for generator-fed systems.

BS 7909 does not replace BS 7671 — it supplements it. Every temporary installation must comply with BS 7671 as the baseline, with BS 7909 adding additional requirements where the temporary nature of the installation creates specific risks (such as cable damage from foot traffic, water ingress from outdoor conditions, or the need for rapid assembly and disassembly).

Free download

Get the BS 7671 A4:2026 Cheat Sheet — free

Every key change in the 2026 amendment on one page. AFDDs, TN-C-S protection, new schedule columns, model forms. Pinned on your van dash.

  • Every regulation change summarised
  • New model forms (EIC + MEIWC)
  • Free PDF — no subscription

We'll email it once. No spam — unsubscribe any time.

02 · Technical Guide

Temporary Supply Design

Designing a temporary electrical supply requires careful planning. Unlike a permanent installation where the supply is established and the installation is built around it, a temporary installation often starts with the question: "Where is the power coming from, and how much do we need?"

  • Supply sources: Temporary installations can be supplied from the public mains (via a temporary builder's supply from the DNO), a portable generator, or a combination of both. For large events, multiple generators may be used in parallel with automatic changeover from mains.
  • Load assessment: Calculate the maximum demand for the temporary installation, applying diversity factors where appropriate. Include all loads: lighting, power tools (or stage equipment for events), heating, welfare facilities, and any specialist equipment. Size the supply, main cables, and protection devices to handle the maximum demand with adequate headroom.
  • Distribution layout: Plan the distribution board layout to minimise cable runs and provide power where it is needed. Use sub-distribution boards to bring power to different areas of the site or event. Each distribution board must have its own main isolator, RCD protection, and circuit protection devices.
  • Cable selection: Cables for temporary installations must be suitable for the environment. Use SWA (Steel Wire Armoured) or equivalent for buried or semi-permanent runs. Use H07RN-F (heavy-duty rubber-sheathed flexible cable) for above-ground runs that may be subject to foot traffic or mechanical damage. All cables must be adequately rated for the current they will carry, taking into account cable sizing factors including ambient temperature and grouping.

Minimum IP ratings by environment

Indicative guidance for distribution equipment, enclosures and connectors. Select for the worst conditions the equipment will actually see (rain, hose-down, ground water), not the conditions on a dry commissioning day.

LocationMinimum IPProtects against
Indoor / under cover, dryIP2X – IP4XFinger/solid-object contact; no specific water protection
Outdoor, general exposureIP44Solid objects >1mm and splashing water from any direction
Heavy rain / hose-down cleaningIP55 – IP65Dust ingress and low-pressure water jets from any direction
Ground level, flood / standing water riskIP67Dust-tight and temporary immersion (up to 1m for 30 min)
03 · Technical Guide

Earthing and Bonding for Temporary Installations

Earthing is the single most critical safety element of a temporary installation. Without effective earthing, protective devices cannot operate in the event of a fault, and exposed metalwork can become live — creating a lethal shock hazard.

  • TT earthing is preferred for outdoor temporary installations. BS 7909 recommends against relying on PME (TN-C-S) earthing for temporary installations in outdoor or high-risk environments. A loss of the PEN conductor in a PME system would put all exposed metalwork at mains potential — in an outdoor environment with wet conditions and metallic structures, this is extremely dangerous.
  • Earth electrodes: For TT earthing, driven earth electrodes (copper clad steel rods) are used to establish an earth connection. The electrode resistance must be measured and verified — a value of 200 ohms or less is typically required to ensure RCD operation within the required disconnection time. Multiple electrodes may be needed to achieve this in poor soil conditions.
  • Bonding: All extraneous conductive parts within the temporary installation must be bonded to the main earthing terminal. This includes metal structures (scaffolding, staging, trusses), metallic water pipes, and any other metalwork that could introduce an earth potential. Main protective bonding conductors are sized per BS 7671 Reg 544.1.1 — not less than half the cross-sectional area of the earthing conductor, with an absolute minimum of 6mm² copper (or 10mm² copper where PME supply conditions apply, per Table 54.8). Supplementary bonding conductors (Reg 544.2) must be at least 2.5mm² copper where mechanically protected, or 4mm² copper where they are not.

Earthing systems for temporary supplies

On construction and demolition sites, a PME (TN-C-S) earthing facility must not be used unless every extraneous-conductive-part is reliably bonded to the main earthing terminal (BS 7671 Reg 704.411.3.1) — in practice this is very difficult to maintain, so TT is the default.

SystemSourceSuitability for temporary work
TTMains or generator with earth electrodePreferred outdoors and on sites. Fault protection relies on RCDs; electrode resistance must be measured and stable.
TN-SDNO TN-S, or generator with earthed star point + separate PEAcceptable where a sound, dedicated earth conductor is available all the way back to the source.
TN-C-S (PME)DNO combined PENRestricted on sites (Reg 704.411.3.1); a lost PEN puts metalwork at mains potential — avoid outdoors.
ITUnearthed generatorContinues to run on a first fault, but requires an insulation monitoring device to alarm before a second fault occurs.

For generator-supplied installations, the earthing arrangement depends on the generator configuration. A generator with an earthed star point typically operates as a TN-S system. An unearthed generator operates as an IT system, which requires an insulation monitoring device to detect first faults. The earthing arrangement must be documented on the single-line diagram and verified by testing before the installation is energised.

04 · Technical Guide

Protection and Overcurrent Devices

Temporary installations require the same level of overcurrent and fault protection as permanent installations — and often more, because the environmental conditions are harsher and the risk of damage is higher.

  • RCD protection: Socket-outlets with a rated current up to 32A require additional protection by a 30mA RCD (BS 7671 Reg 411.3.3), with limited exceptions permitted by that regulation. For TT earthing systems, RCD protection is essential for fault protection: earth fault loop impedance via driven electrodes is typically too high for overcurrent devices alone to achieve the required disconnection times, so RCDs are the primary means of achieving disconnection. The RCD type must be matched to the load it protects (BS 7671 Reg 531.3.3) — see the table below.
  • MCBs and RCBOs: Each circuit must be protected by an appropriately rated MCB or RCBO. The protective device must be selected to provide both overload protection and short-circuit protection. The breaking capacity of the protective device must be equal to or greater than the prospective fault current at the point of installation.
  • Discrimination: Where multiple levels of RCD protection are used (for example, a 100mA time-delayed RCD at the main board and 30mA RCDs at sub-boards), discrimination must be achieved to ensure that a fault on one circuit only trips the nearest RCD, not the upstream one.

RCD type selection (Reg 531.3.3)

Choose the lowest type that fully covers the residual-current waveform the load can produce. Type AC may only serve fixed equipment with no DC content.

TypeDetectsTypical temporary-installation loads
ACSinusoidal AC residual current onlyFixed resistive loads with no DC content only (e.g. simple heaters, filament lamps). Not suitable as a default for modern electronics.
AAC + pulsating DC residual currentGeneral socket outlets, single-phase tools, most LED and switch-mode loads — the practical minimum for modern equipment.
FAs Type A + composite/mixed-frequency residual currentsSingle-phase variable-speed drives, dimmers and stage equipment producing mixed-frequency residual currents.
BAs Type F + smooth DC residual currents (incl. 3-phase rectified)Three-phase drives, EV charge points and other equipment that can produce smooth DC fault current.

The type and rating of RCD must be carefully selected for the loads being protected. Modern entertainment lighting and stage equipment often contain electronic drivers that produce pulsating DC or composite fault currents — a standard Type AC RCD will not detect these. Use Type A as a minimum for most modern equipment; Type F where variable-speed drives or mixed-frequency loads are present; and Type B where smooth DC components exist (Reg 531.3.3).

Try Elec-Mate free for 7 days

16 certificate types, 70+ calculators, RAMS, quoting, invoicing, AI agents, and 46+ training courses — from £6.99/mo.

Start free trial
Download on the App StoreGet it on Google Play
05 · Technical Guide

Testing and Verification of Temporary Installations

Every temporary installation must be inspected and tested before it is energised for the first time. The testing regime is the same as for a permanent installation under BS 7671 Chapter 64 (Initial Verification), with additional visual checks for the temporary-specific risks.

  1. Visual inspection: Check all cables for damage; verify all connections are tight and properly terminated; confirm IP ratings of enclosures are appropriate for the environment; check cable routing for trip hazards, water exposure, and mechanical damage risks; verify labelling of all circuits and distribution boards.
  2. Dead tests: Continuity of protective conductors (including main and supplementary bonding); continuity of ring final circuits (if applicable); insulation resistance per Reg 643.3 (for circuits up to and including 500V, test at 500V DC with a minimum acceptable value of 1.0 MΩ — BS 7671 Table 64); polarity checks at all points.
  3. Live tests: Earth fault loop impedance at the furthest point of each circuit (to verify disconnection times); prospective fault current at the origin; RCD testing (trip time at rated current, 5x rated current, and ramp test); voltage and frequency at the origin.
  4. Functional tests (Reg 643.10): Verify all switching and isolation devices operate correctly; test emergency stop buttons and emergency lighting (where installed); verify that generator changeover systems operate correctly (where installed).

Complete electrical certificates on your phone

Elec-Mate lets you create EIC, EICR, and Minor Works certificates directly on site. AI board scanner reads distribution board details…

Try it free for 7 days
Download on the App StoreGet it on Google Play
06 · Technical Guide

Documentation Requirements

Temporary installations require the same documentation as permanent installations, plus additional records specific to the temporary nature of the work. For event installations under BS 7909, the documentation requirements are particularly detailed.

  • Single-line diagram: A schematic showing the supply source, main distribution, sub-distribution, cable types and sizes, protective devices, earthing arrangement, and all loads. This is the reference document for anyone working on or maintaining the installation.
  • Electrical Installation Certificate (EIC): Issued for the initial installation, confirming compliance with BS 7671. Must be completed before the installation is energised.
  • Schedule of test results: All dead and live test results recorded in the standard format. Must accompany the EIC.
  • Risk assessment and method statement (RAMS): Covering the installation, commissioning, operation, and decommissioning of the temporary electrical system. Must be completed before work begins.
  • Periodic inspection records: For installations that remain in place for extended periods, regular inspection and test records (EICR) at intervals not exceeding 3 months.

For entertainment events, BS 7909 also recommends a site-specific electrical safety policy, an emergency procedure document, and a handover document for the event organisers confirming that the installation is safe for use.

Generate RAMS and certificates with AI

Elec-Mate's AI Health and Safety agent generates complete RAMS documents for temporary installations, while the certificate app produces EIC, EICR…

Try it free for 7 days
Download on the App StoreGet it on Google Play
07 · Technical Guide

Construction Sites vs Events: Key Differences

While the fundamental principles of temporary installation design are the same, there are important differences between construction site installations and entertainment/event installations:

Construction Sites

  • BS 7671 Section 704 applies directly
  • 110V CTE reduced low voltage strongly preferred for portable tools (Reg 704.410.3.10)
  • 3-month inspection intervals
  • CDM 2015 duties apply
  • Users are trained electricians and trades

Entertainment and Events

  • BS 7909 supplements BS 7671
  • 230V and 400V commonly used for lighting rigs
  • Inspection before each event
  • Public safety is the primary concern
  • Users may include untrained public

Note on Section 704 scope (Reg 704.1.1): The particular requirements of Section 704 do not apply to administrative locations on construction sites — offices, cloakrooms, meeting rooms, canteens, restaurants, dormitories, and toilets are explicitly excluded. Those areas are treated as ordinary installations under the general requirements of BS 7671.

The public safety dimension of event installations cannot be overstated. On a construction site, the users of the electrical system are (or should be) trained workers who understand the risks. At an event, members of the public — including children — may come into proximity with the temporary electrical installation. This demands higher standards of cable protection, enclosure security, and signage. All accessible distribution equipment must be locked or secured to prevent public access.

Frequently Asked Questions About Temporary Installations

What electricians say

Verified reviews from the UK App Store.

One App for Everything!

Elec-Mate is my go to app for business and electrical work. It's feature rich without feeling cluttered. A true all in one app for quotes, certs, calculations, RAMS, EICRs, and more. I use it every day without fail, and it makes my workflow much smoother since I'm not jumping between apps anymore. The price-to-feature ratio is excellent. Any issues I've had, the developer responds within the hour and usually fixes them the same day. 100% recommend.

Apple App Store · GBR

Fantastic app for electricians

I've used the app and the web based version for a while now and it's well worth the investment. If you're an apprentice or experienced Spark give it a go, you won't be disappointed.

Apple App Store · GBR

Absolutely amazing

I've been using Elec-Mate for a while now, and honestly, it's one of the best apps I've ever downloaded. Every aspect of it feels thoughtfully designed, from the clean and intuitive interface to the powerful features that make everything so easy to manage. It's clear that a lot of care and attention went into building this app, and it shows in every detail.

Apple App Store · GBR

Trusted by electricians across the UK

Real feedback from real sparks

“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”

Daniel Palmer

Sole Trader · DP Electrical

“I've won two contracts this month because I could turn quotes around same-day with the AI cost engineer.”

Nathan Perry

Electrician · NP Electrical Services

“The study centre got me through my AM2. Mock exams and flashcards are brilliant.”

Jake Pizey

3rd Year Apprentice · Apprentice

7-Day Free Trial — Cancel Anytime, No Hassle

Certificates and RAMS for Temporary Installations

Create EIC, EICR, and Minor Works certificates on your phone. Generate RAMS and risk assessments with AI. Designed for electricians working on temporary installations. 7-day free trial.

“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”

Daniel Palmer, DP Electrical

From £6.99/mo after trial — less than a coffee a week

or download the app
Download on the App StoreGet it on Google Play
7 days free, then from £6.99/moCancel in one tap — no calls, no hassleiOS, Android & WebBS 7671 compliant
16
Certificate Types
70+
Calculators
46+
Training Courses
8
AI Agents

1,000+ electricians · From £6.99/mo after trial

We use cookies to improve the app and measure what works. Cookie Policy