2382-26 REVISION

18th Edition Exam Questions and Answers

50 questions for the City & Guilds 2382-26 (BS 7671:2018+A4:2026), including worked calculations, set across all eight exam outcomes, with a model answer and the regulation to look up under every one.

£0 today · 7 days free · cancel in two taps

40 min readUpdated 2026-11-27Andrew Moore, Founder of Elec-Mate

Written and reviewed by Andrew Moore, founder of Elec-Mate, against BS 7671:2018+A4:2026 and the City & Guilds 2382-26 qualification handbook (April 2026).

ShareXinW
Follow

The short answer

What questions come up in the 18th Edition exam?

The City & Guilds 2382-26 asks 60 multiple-choice questions on BS 7671:2018+A4:2026 in 120 minutes, open book, with a pass mark of about 60%. Most marks come from Part 4 protection for safety (15) and Part 5 selection and erection (14), then Part 8 and the appendices (8), Part 7 special locations (7) and Part 3 (6).

3,100+

UK electricians

“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”

Daniel Palmer, DP Electrical · 5 out of 5

Key takeaways

  1. 01The City & Guilds 2382-26 is one online multiple-choice test: 60 questions in 120 minutes, open book with BS 7671:2018+A4:2026, pass mark about 60%.
  2. 02Part 4 (protection for safety, 15 questions) and Part 5 (selection and erection, 14 questions) carry almost half the marks between them.
  3. 03It is a test of finding things fast. Know where Table 41.3, Table 64, Appendix 3 and Appendix 4 are, and tab them.
  4. 04A non-programmable calculator is allowed, so expect Zs checks, Ib ≤ In ≤ Iz and the adiabatic equation.
  5. 05Your book may have tabs, highlighting and short cross-references, but no written notes, sample questions or extra diagrams.

01 · 2382-26 Revision

How the 2382-26 exam works, and how to use these questions

The City & Guilds Level 3 Award in Requirements for Electrical Installations BS 7671:2018 (2382-26) is assessed by one online multiple-choice test. You have 120 minutes for 60 questions, the pass mark is set at about 60%, and the result is pass or fail. It is open book: you take in BS 7671:2018 (Amendment 4:2026) and a non-programmable calculator. Your copy may have bookmarks or numbered tabs, highlighting and short cross-references, but not detailed notes, sample questions or extra diagrams. Source: City & Guilds 2382-26 qualification handbook v1.0 (April 2026).

City & Guilds publishes how the 60 questions are split across the eight outcomes: Part 1 scope and principles 4, Part 2 definitions 2, Part 3 general characteristics 6, Part 4 protection for safety 15, Part 5 selection and erection 14, Part 6 inspection and testing 4, Part 7 special locations 7, and Part 8 with the appendices 8. The 50 questions below follow the same eight areas in roughly the same proportions.

The real paper is multiple choice, but every question on it is really two questions: where is this in the book, and what does it say? So cover each answer, find the regulation yourself, then compare. Under every answer is the regulation or table to look up. These 50 sit alongside our full 18th Edition question bank: each Part below ends with links to the matching topic drills, multiple choice with a worked answer on every question. When you are ready to work against the clock, sit the free 18th Edition mock exam, and see the 18th Edition exam tips for how to tab your book.

Answers are showing.

Free download · PDF

Get the free BS 7671 A4:2026 Cheat Sheet

Every key change in the 2026 amendment on one page. AFDDs, TN-C-S protection, new schedule columns, model forms. Pinned on your van dash.

  • Every regulation change summarised
  • New model forms (EIC + MEIWC)
  • Free PDF, no subscription

We'll email it once. No spam, and you can unsubscribe any time.

02 · 2382-26 Revision

Quick find: the tables and appendices worth tabbing

These are the tables and appendices the answers below send you to most. Names are as they appear in the list of tables and contents of BS 7671:2018+A4:2026. Tab them before the exam and practise turning to each one without the index.

Table 41.1

Maximum disconnection times

Table 41.2

Maximum earth fault loop impedance (Zs) for fuses, 0.4 s

Table 41.3

Maximum earth fault loop impedance (Zs) for circuit-breakers

Table 41.5

Maximum earth fault loop impedance (Zs) for non-delayed and 'S' type RCDs

Table 43.1

Values of k for common materials, for the effects of fault current

Table 52.1

Requirements for a cable concealed in a wall or partition

Table 52.3

Minimum cross-sectional area of conductors

Table 54.3

Values of k for a protective conductor incorporated in a cable

Table 54.7

Minimum cross-sectional area of protective conductor in relation to the associated line conductor

Table 54.8

Minimum main protective bonding conductor in relation to the PEN conductor of the supply

Table 64

Minimum values of insulation resistance

Table 443.2

Required rated impulse voltage of equipment (Uw)

Appendix 3

Time/current characteristics of overcurrent protective devices

Appendix 4

Current-carrying capacity and voltage drop for cables (Tables 4Ab, 4B1, 4C1 and the cable tables)

Appendix 5

Classification of external influences

Appendix 6

Model forms for certification and reporting

Appendix 15

Ring and radial final circuit arrangements, Regulation 433.1

Appendix 17 (energy efficiency) was deleted by A4:2026. Energy efficiency is now Chapter 81 in Part 8, which is informative.

03 · 2382-26 Revision

Part 1: scope, object and fundamental principles

Q1. State the voltage and frequency limits for circuits covered by BS 7671 and say where in the book you would confirm them.

BS 7671 covers circuits supplied at nominal voltages up to and including 1000 V AC or 1500 V DC. For AC, the preferred frequencies taken into account are 50 Hz, 60 Hz and 400 Hz, although other frequencies for special purposes are not excluded. This is Regulation 110.1.2(a), in Chapter 11 (Scope) of Part 1. Regulation 110.1.2(b) also brings in circuits operating at voltages exceeding 1000 V where they are derived from an installation not exceeding 1000 V AC, for example discharge lighting. Regulation 110.1.1 lists the types of installation covered, which include electric vehicle charging and stationary secondary batteries for storage and supply of electrical installations.

Where to find it: BS 7671 Regulations 110.1.1 and 110.1.2

Q2. Regulation 131.2 sets out the fundamental principle of protection against electric shock. Explain the difference between basic protection and fault protection, and list the methods by which fault protection can be achieved.

Basic protection protects persons and livestock against dangers from contact with live parts. Fault protection protects them against dangers from contact with exposed-conductive-parts during a fault. Regulation 131.2.2 says fault protection can be achieved by preventing a fault current passing through the body, limiting the magnitude of that current to a non-hazardous value, or limiting its duration to a non-hazardous time period. It adds that protective equipotential bonding is one of the important principles for safety. Part 2 backs this up: basic protection is protection under fault-free conditions and fault protection is protection under single fault conditions.

Where to find it: BS 7671 Regulations 131.2.1 and 131.2.2; Part 2 definitions

Q3. A designer wants to use an item of equipment outside the scope of its product standard. What does BS 7671 require, and how must this be recorded?

The designer, or other person responsible for specifying the installation, must confirm that the equipment provides at least the same degree of safety as compliance with the Regulations, and the use must be recorded as a departure on the electrical certification specified in Part 6. This is Regulation 133.1.3 in Chapter 13. Part 2 defines a departure as a deliberate decision not to comply fully with BS 7671, where the designer declares the resulting safety is not less than full compliance. Regulation 133.1.2 covers equipment with no applicable standard: it is selected by special agreement and recorded as an agreed departure. Regulation 133.5 applies the same safety test to new materials and inventions.

Where to find it: BS 7671 Regulations 133.1.2, 133.1.3 and 133.5; Part 2 definition of Departure

Q4. BS 7671 is a British Standard rather than legislation. Explain how it relates to the Electricity at Work Regulations 1989 and where in the book this relationship is described.

BS 7671 is not itself a statutory instrument, but the Health and Safety Executive regards installations that conform to BS 7671:2018+A4:2026 as likely to achieve conformity with the relevant parts of the Electricity at Work Regulations 1989. This is stated in the Note by the Health and Safety Executive at the front of the book. The Introduction to Amendment 4:2026 adds that compliance with a British Standard cannot confer immunity from legal obligations. Appendix 2 lists the statutory regulations that apply to different classes of installation, and notes that failure to comply with Chapter 13 means the distributor is not compelled to commence or, in certain circumstances, to continue to give a supply to that installation. Section 114 in Chapter 11 also deals with the relationship between the Regulations and statutory regulations.

Where to find it: BS 7671 Note by the Health and Safety Executive; Introduction to Amendment 4:2026; Appendix 2

More practice on this Part, with a worked answer on every question

04 · 2382-26 Revision

Part 2: definitions

Q5. Using the definitions in Part 2, distinguish between an exposed-conductive-part and an extraneous-conductive-part, and state which regulations deal with connecting each of them.

An exposed-conductive-part is a conductive part of equipment which can be touched and is not normally live, but which can become live under fault conditions. An extraneous-conductive-part is a conductive part liable to introduce a potential, generally Earth potential, and not forming part of the electrical installation. Regulation 411.3.1.1 requires exposed-conductive-parts to be connected to a protective conductor. Regulation 411.3.1.2 requires extraneous-conductive-parts liable to introduce a dangerous potential difference to be connected to the main earthing terminal by protective bonding conductors, giving examples such as metallic water and gas installation pipes and exposed metallic structural parts of the building.

Where to find it: BS 7671 Part 2 definitions; Regulations 411.3.1.1 and 411.3.1.2

Q6. Part 2 defines skilled, instructed and ordinary persons. Explain the difference and show how these definitions affect the RCD exception in Regulation 411.3.3.

A skilled person (electrically) has, as appropriate to the work, adequate education, training and practical skills, and can perceive risks and avoid hazards which electricity can create. An instructed person (electrically) is adequately advised or supervised by a skilled person so they can do the same. An ordinary person is neither. In Regulation 411.3.3, the exception allowing RCD protection to be omitted for socket-outlets under item (b) needs a documented risk assessment undertaken with the involvement of a skilled person (electrically). NOTE 1 to that regulation makes clear that an ordinary person instructed in the use of the installation does not become an instructed person (electrically).

Where to find it: BS 7671 Part 2 definitions (Person); Regulation 411.3.3 and NOTE 1

Q7. Define overcurrent, overload current and short-circuit current as given in Part 2, and state where in BS 7671 protection against them is covered.

Overcurrent is a current exceeding the rated value; for conductors the rated value is the current-carrying capacity. Overload current is an overcurrent occurring in a circuit which is electrically sound. Short-circuit current is an overcurrent resulting from a fault of negligible impedance between live conductors having a difference in potential under normal operating conditions. Protection is covered in Chapter 43, with Section 433 for overload current and Section 434 for fault current. Part 2 also defines current-carrying capacity as the maximum current a conductor can carry under specified conditions without its steady-state temperature exceeding a specified value. That is the Iz used in Regulation 433.1.1.

Where to find it: BS 7671 Part 2 definitions; Chapter 43, Sections 433 and 434

More practice on this Part, with a worked answer on every question

05 · 2382-26 Revision

Part 3: assessment of general characteristics

Q8. Before designing an installation, which characteristics of the supply must be determined under Regulation 313.1, and how may they be obtained?

Regulation 313.1 requires these to be determined by calculation, measurement, enquiry or inspection: the nominal voltage and its characteristics, including harmonic distortion; the nature of the current and frequency; the prospective short-circuit current at the origin; the earth fault loop impedance of the part of the system external to the installation, Ze; the suitability for the requirements of the installation, including maximum demand; and the type and rating of the overcurrent protective device at the origin. They are ascertained for an external supply and determined for a private source, and apply equally to safety services and standby supplies. The note refers to Appendix 2, Item 2, for information distributors should provide on request.

Where to find it: BS 7671 Regulation 313.1; Appendix 2 Item 2

Q9. What is a TN-C-S (PNB) system, and what does BS 7671 say about where the PEN conductor is connected to an earth electrode?

A TN-C-S (PNB) system is one in which neutral and protective functions are combined in a single conductor in part of the system, earthed at a single point. Part 2 describes protective neutral bonding as an arrangement where there is only one point in the network at which consumers' installations are connected to a single source of voltage. It is shown in Figure 3.9B under Regulation 312.2.1.1, and the Introduction to Amendment 4:2026 confirms that this regulation now includes the PNB figure and requirements. NOTE 2 to the figure says the PEN conductor is connected to an earth electrode at a point remote from the transformer, as close as practicable to the consumer's supply terminals.

Where to find it: BS 7671 Regulation 312.2.1.1, Figure 3.9B and NOTES; Part 2 definition of PNB

Q10. An external influence is given the code AD4. Explain how external influence codes are built up, what AD4 means and the degree of protection associated with it.

Each condition of external influence is coded as two capital letters and a number. The first letter gives the general category (A is environment, B is utilization and C is construction of buildings), the second letter gives the nature of the influence, and the number gives the class. AD is presence of water and AD4 is splashes, for which the Appendix 5 table gives IPX4. Chapter 32 refers you to Chapter 51 and Appendix 5, where the codes are listed. Part 7 uses the same codes, for example Regulation 708.512.1.1 requires a degree of protection of at least IPX4 to protect against water splashes (AD4).

Where to find it: BS 7671 Chapter 32; Appendix 5; Regulation 708.512.1.1

Q11. Chapter 33 requires an assessment of compatibility. List characteristics of equipment that must be assessed and state who must be consulted where the supply is from an external source.

Regulation 331.1 requires an assessment of any characteristics of equipment likely to have harmful effects on other electrical equipment or other services, or likely to impair the supply. The examples listed are transient overvoltages, undervoltage, unbalanced loads, rapidly fluctuating loads, starting currents, harmonic currents, earth leakage current, excessive PE conductor current not due to a fault, DC feedback, high-frequency oscillations, the need for additional connections to Earth and power factor. For an external source of energy, the distributor must be consulted about any equipment likely to have a significant influence on the supply. Regulation 332.1 adds that all equipment must meet the relevant EMC standard.

Where to find it: BS 7671 Regulations 331.1 and 332.1

Q12. List the electrical sources for safety services recognized in Chapter 35, and state what Chapter 36 requires regarding continuity of service.

Regulation 351.1 recognizes four sources: primary batteries; stationary secondary batteries; other generating sets independent of the normal supply; and a separate feeder of the supply network that is effectively independent of the normal feeder. NOTE 2 gives examples of safety services, such as emergency escape lighting and fire detection and fire alarm systems. Regulation 361.1 requires an assessment for each circuit of any need for continuity of service during the intended life of the installation, for example life-support systems. The characteristics to be considered are system earthing, selectivity of protective devices, number of circuits, multiple sources of supply and use of monitoring devices.

Where to find it: BS 7671 Regulations 351.1 and 361.1

More practice on this Part, with a worked answer on every question

06 · 2382-26 Revision

Part 4: protection for safety

Q13. Under Regulation 411.3.3, which socket-outlets and mobile equipment require additional protection by an RCD, and when may the risk assessment exception be used?

In AC systems, an RCD with a rated residual operating current not exceeding 30 mA is required for: (a) socket-outlets rated up to 32 A where they are liable to be used by ordinary persons (BA1) or children (BA2); (b) socket-outlets rated up to 32 A in other locations; and (c) mobile equipment rated up to 32 A for use outdoors. An exception is permitted for (b) only, never (a) or (c), where a documented risk assessment involving a skilled person (electrically) determines RCD protection is not necessary. That risk assessment must be provided with the electrical installation certificate. Regulation 415.1.1 explains the purpose: 30 mA RCDs are recognized as additional protection.

Where to find it: BS 7671 Regulations 411.3.3 and 415.1.1

Q14. State the maximum disconnection times for a 230 V AC final circuit in a TN system and in a TT system, the final circuits to which they apply, and the time permitted for a distribution circuit in a TN system.

Table 41.1 gives 0.4 s for a TN system and 0.2 s for a TT system for a nominal voltage to earth (Uo) of 230 V AC. Regulation 411.3.2.2 applies these times to final circuits rated up to 63 A with one or more socket-outlets, and up to 32 A supplying only fixed connected current-using equipment. Regulation 411.3.2.3 permits a disconnection time not exceeding 5 s in a TN system for a distribution circuit and for any circuit not covered by 411.3.2.2. Table 41.1 sits directly after Regulation 411.3.2.2 in Chapter 41.

Where to find it: BS 7671 Regulations 411.3.2.2 and 411.3.2.3; Table 41.1

Q15. A ring final circuit in a TN-C-S installation is protected by a 32 A Type B circuit-breaker to BS EN 60898. The earth fault loop impedance measured at the furthest point, at ambient temperature, is 1.15 ohms. Using Table 41.3 and the method in Appendix 3, does the reading demonstrate compliance with the 0.4 s disconnection time?

No, the reading does not demonstrate compliance.

  1. Step 1: Table 41.3(a) gives a maximum Zs of 1.37 ohms for a 32 A Type B circuit-breaker.
  2. Step 2: NOTE 2 to the table says the values apply with line conductors at their maximum permitted operating temperature, so a reading at ambient temperature must be adjusted.
  3. Step 3: Appendix 3 applies a factor of 0.8 for the increase in conductor resistance with temperature: 0.8 x 1.37 = 1.10 ohms (1.096 rounded).
  4. Step 4: The measured 1.15 ohms is greater than 1.10 ohms.

Conclusion: although below the table figure, the reading fails the Appendix 3 check and the circuit needs investigating.

Where to find it: BS 7671 Regulation 411.4.202; Table 41.3(a) and NOTE 2; Appendix 3

Q16. A TT installation has a value of RA (earth electrode plus the protective conductor connecting it to the exposed-conductive-parts) of 120 ohms. Final circuits are protected by 30 mA RCDs at 230 V. Check compliance with Regulation 411.5.3 and comment on the electrode value.

The installation complies.

  1. Step 1: Regulation 411.5.3(b) requires RA x IΔn not to exceed 50 V.
  2. Step 2: 120 x 0.03 = 3.6 V.
  3. Step 3: 3.6 V is well below 50 V, so condition (b) is met.
  4. Step 4: Condition (a) still applies: the RCD must disconnect within the time in Table 41.1, which is 0.2 s for a TT final circuit at 230 V.
  5. Step 5: Table 41.5 allows a Zs of up to 1667 ohms for a 30 mA RCD, but NOTE 2 warns that an electrode resistance exceeding 200 ohms may not be stable.

Conclusion: 120 ohms satisfies 411.5.3 and is below that 200 ohm guide.

Where to find it: BS 7671 Regulation 411.5.3; Table 41.1; Table 41.5 and NOTE 2

Q17. A radial circuit has a design current (Ib) of 27 A and is protected by a 32 A circuit-breaker to BS EN 60898. After rating factors are applied, the cable's current-carrying capacity (Iz) is 36 A. Show whether the circuit meets Regulation 433.1.1 for overload protection.

Yes, the circuit complies.

  1. Step 1: Condition (a) of Regulation 433.1.1 requires In to be not less than Ib. 32 A is not less than 27 A, so (a) is met.
  2. Step 2: Condition (b) requires In not to exceed the lowest Iz of the circuit conductors. 32 A does not exceed 36 A, so (b) is met.
  3. Step 3: Condition (c) requires the current causing effective operation of the device (I2) not to exceed 1.45 times Iz. Regulation 433.1.201 states that for a circuit-breaker to BS EN 60898, compliance with (a) and (b) also gives compliance with (c).

Conclusion: Ib ≤ In ≤ Iz (27 ≤ 32 ≤ 36), so overload protection is satisfied.

Where to find it: BS 7671 Regulations 433.1.1 and 433.1.201

Q18. An existing circuit is protected by a 30 A semi-enclosed fuse to BS 3036. Calculate the minimum current-carrying capacity (Iz) the cable must have to satisfy the overload requirements of Regulation 433.1.1.

The cable needs an Iz of at least 41.4 A.

  1. Step 1: Regulation 433.1.202 states that with a semi-enclosed fuse to BS 3036, condition (c) of 433.1.1 is met if the fuse's rated current does not exceed 0.725 times the current-carrying capacity of the lowest rated conductor.
  2. Step 2: So In ≤ 0.725 x Iz, which rearranges to Iz ≥ In / 0.725.
  3. Step 3: 30 / 0.725 = 41.38 A, rounded up to 41.4 A.

Conclusion: a cable with an Iz below 41.4 A would fail condition (c), even where it satisfies conditions (a) and (b). NOTE 1 to Regulation 433.1.1 points BS 3036 users to Regulation 433.1.202.

Where to find it: BS 7671 Regulations 433.1.1 NOTE 1 and 433.1.202

Q19. Where does Regulation 421.1.7 require arc fault detection devices (AFDDs), and what does it say about where they are placed?

AFDDs conforming to BS EN 62606 are required for single-phase AC final circuits supplying socket-outlets rated up to 32 A in high rise residential buildings, houses in multiple occupation, purpose-built student accommodation and care homes. NOTE 1 takes a high rise residential building to be over 18 m in height or in excess of six storeys, whichever is met first. For all other premises, AFDDs are recommended for the same circuits. Where used, AFDDs must be placed at the origin of the circuit, although NOTE 2 allows another location for busbar and powertrack systems. Using AFDDs does not remove the need for other measures in BS 7671. The Introduction to Amendment 4:2026 confirms item (a) now reads high rise residential buildings.

Where to find it: BS 7671 Regulation 421.1.7 and NOTES 1 and 2; Introduction to Amendment 4:2026

Q20. What may be installed in a firefighting shaft or protected stairway of a protected escape route, when are cables deemed to be outside a protected escape route, and what smoke and gas limits apply to cables in such routes?

Regulation 422.2.201 permits cables or other electrical equipment in a firefighting shaft or protected stairway only as part of an essential fire safety or related safety system, general needs lighting, or socket-outlets provided for cleaning or maintenance. Cables meeting Regulation 422.2.1 may be installed in a protected corridor. Under 422.2.202, cables are deemed outside the protected escape route where installed in a fire-resisting enclosure with fire resistance not less than that of the compartment they pass through, or that specified by the fire engineer. Regulation 422.2.1 requires limited smoke production, with a minimum of 60 % light transmittance, and halogen acid gas content not exceeding 0.5 %.

Where to find it: BS 7671 Regulations 422.2.201, 422.2.202 and 422.2.1

Q21. Under Regulation 443.4, when must protection against transient overvoltages due to indirect lightning strokes be provided, and when may it be omitted?

Protection must be provided where the consequence of the overvoltage could result in (a) serious injury to, or loss of, human life, or (c) significant financial or data loss. Item (b) has been deleted. In all other cases it must still be provided unless the owner of the installation declares it is not required, because any loss or damage is tolerable and they accept the risk of damage to equipment and any consequential loss. Regulation 443.4.2 adds that protection must be considered for equipment likely to produce switching overvoltages, such as motors, transformers and capacitor banks. Table 443.2 sets required rated impulse voltages: for a 230/400 V installation, 4 kV for category III equipment such as distribution boards.

Where to find it: BS 7671 Regulations 443.4.1 and 443.4.2; Table 443.2

Q22. Chapter 46 covers isolation. State the requirements for the main switch of an installation, how isolating devices must be protected against unintentional closure, and the rules on isolating the PEN and neutral conductors.

Regulation 462.1.201 requires a main linked switch or linked circuit-breaker as near as practicable to the origin, for switching the supply on load and for isolation. A main switch intended for operation by ordinary persons, for example in a household, must interrupt both live conductors of a single-phase supply. Regulation 462.3 requires isolating devices to prevent unintentional or inadvertent closure, for example by a lockable space or enclosure, padlocking, or location next to the equipment. Under 461.2, the PEN conductor must not be isolated or switched. In TN-C-S and TN-S systems the neutral need not be isolated where protective equipotential bonding is installed and either the neutral is reliably connected to Earth by a low resistance, or the distributor declares that the PEN or neutral of the supply is reliably connected to Earth by a low resistance, so as to meet the Chapter 41 disconnection times.

Where to find it: BS 7671 Regulations 461.2, 462.1.201 and 462.3

Q23. Distinguish between switching off for mechanical maintenance and emergency switching off, giving the key requirements of Sections 464 and 465.

Switching off for mechanical maintenance is required where mechanical maintenance may involve a risk of physical injury. Part 2 defines mechanical maintenance as the replacement, refurbishment or cleaning of lamps and non-electrical parts of equipment, plant and machinery. Regulation 464.1 requires all live conductors to be disconnected, except as allowed by 461.2, by a device suitable for isolation. Regulation 464.2 requires means to prevent inadvertent reactivation unless the switching device is continuously under the control of the person doing the maintenance. Emergency switching off, under 465.1, is to remove an unexpected danger. Regulation 465.3 requires it to act as directly as possible on the supply conductors, with one single action interrupting the appropriate supply.

Where to find it: BS 7671 Sections 464 and 465; Part 2 definition of Mechanical maintenance

Q24. In domestic premises, which final circuits other than socket-outlet circuits need 30 mA RCD protection under Chapter 41, and why can an RCD not be relied on as the only protective measure?

Regulation 411.3.4 requires additional protection by an RCD with a rated residual operating current not exceeding 30 mA for AC final circuits supplying luminaires within domestic (household) premises. Regulation 411.3.3(c) also requires it for mobile equipment rated up to 32 A for use outdoors. Regulation 415.1.1 recognizes such RCDs as additional protection in the event of failure of the provision for basic protection or fault protection, or carelessness by users. However, Regulation 415.1.2 states that RCDs are not recognized as a sole means of protection. One of the protective measures in Sections 411 to 414 must still be applied, for example automatic disconnection of supply with protective earthing and bonding. Both regulations are in Chapter 41, with Section 415 covering additional protection.

Where to find it: BS 7671 Regulations 411.3.4, 415.1.1 and 415.1.2

More practice on this Part, with a worked answer on every question

In the app

Practise with unlimited mock exams

AI-generated mocks, instant marking, and explanations on every question: targeted at your weakest topics. From £6.99/mo.

Download on the App StoreGet it on Google Play

07 · 2382-26 Revision

Part 5: selection and erection of equipment

Q25. A radial circuit is wired in 70 °C thermoplastic twin and earth cable with a 1.5 mm² copper protective conductor. The earth fault current is 400 A and the protective device disconnects in 0.1 s. Using the adiabatic equation, is the protective conductor large enough?

Yes. The minimum size works out at about 1.10 mm², so 1.5 mm² is adequate.

  1. Step 1: Regulation 543.1.3 gives S = √(I²t) ÷ k, and the note says the equation applies for disconnection times not exceeding 5 s.
  2. Step 2: the protective conductor is incorporated in a cable, so take k from Table 54.3: 115 for copper with 70 °C thermoplastic insulation.
  3. Step 3: I²t = 400² × 0.1 = 16,000, and √16,000 = 126.5.
  4. Step 4: S = 126.5 ÷ 115 = 1.10 mm².

Conclusion: 1.10 mm² is less than 1.5 mm², so the conductor complies. Where the formula gives a non-standard size, the next larger standard size must be used.

Where to find it: BS 7671 Regulation 543.1.3; Table 54.3

Q26. A 32 A circuit-breaker protects a circuit in 70 °C thermoplastic multicore cable, bunched with two other circuits in an ambient temperature of 35 °C. Part of the run is totally surrounded by thermal insulation for more than 0.5 m. What minimum tabulated current-carrying capacity (It) does the cable need?

It must be at least 97.3 A.

  1. Step 1: Appendix 4, section 5, says divide the protective device rating (In) by each applicable rating factor.
  2. Step 2: Table 4B1 gives Ca = 0.94 at 35 °C for 70 °C thermoplastic insulation.
  3. Step 3: Table 4C1 gives Cg = 0.70 for three circuits bunched.
  4. Step 4: Regulation 523.9 says that for a single cable totally surrounded by thermal insulation for 0.5 m or more, in the absence of more precise information, the current-carrying capacity is taken as 0.5 times its Reference Method C (clipped direct) value, so Ci = 0.5. Applying it together with the grouping factor assumes the worst case, where the bunching and the insulation are on the same length of cable.
  5. Step 5: It = 32 ÷ (0.94 × 0.70 × 0.5) = 32 ÷ 0.329 = 97.3 A.

Conclusion: select a cable rated at least 97.3 A for Reference Method C, or reroute it clear of the insulation.

Where to find it: BS 7671 Appendix 4 section 5; Table 4B1; Table 4C1; Regulation 523.9

Q27. An installation is supplied directly from a public low voltage distribution system at 230 V. A power circuit, together with the distribution circuit feeding it, has a total wiring length of 160 m and a calculated voltage drop of 12 V. Does it meet the voltage drop limit in Appendix 4?

Yes, just.

  1. Step 1: Regulation 525.202 deems the voltage requirements met if the drop does not exceed Appendix 4, section 6.4. Table 4Ab there gives 5% for other uses on an installation supplied directly from a public low voltage system.
  2. Step 2: where wiring systems are longer than 100 m, the limit may be increased by 0.005% per metre beyond 100 m, up to a cap given in the table.
  3. Step 3: 160 m minus 100 m = 60 m, and 60 × 0.005% = 0.3%, which is within the cap, so the limit becomes 5.3%.
  4. Step 4: 5.3% of 230 V = 12.19 V.

Conclusion: 12 V is below 12.19 V, so the circuit complies. The drop itself is found from the tabulated mV/A/m × length × design current.

Where to find it: BS 7671 Regulation 525.202; Appendix 4 section 6.4, Table 4Ab

Q28. A socket-outlet circuit is to be concealed 25 mm deep in a plastered block wall that has no metallic parts. Using Table 52.1, what are the options for the cable, and what is a prescribed zone?

Below 50 mm deep in a wall without metallic parts, Table 52.1 requires the cable either to be installed in a prescribed zone and given additional protection by an RCD with the characteristics of Regulation 415.1.1 (not exceeding 30 mA), or to comply with Regulation 522.6.204, for example an earthed metallic covering, earthed conduit or trunking, mechanical protection against penetration by nails and screws, or SELV or PELV. A prescribed zone is within 150 mm of the top of the wall or of an angle formed by two adjoining walls, or runs horizontally and vertically from an accessory, point or switchgear on the wall. Regulation 522.6.202 sends you to Table 52.1, which now holds these requirements following A4.

Where to find it: BS 7671 Regulation 522.6.202; Table 52.1; Regulation 522.6.204

Q29. Cables are to be clipped direct across the ceiling of an escape corridor. Why are plastic cable clips alone not acceptable, and what does Regulation 521.10.202 require?

Regulation 521.10.202 requires wiring systems to be supported so that they will not be liable to premature collapse in the event of a fire. Note 3 states that this precludes non-metallic clips or cable ties as the sole means of support where cables are clipped direct to exposed surfaces or suspended under cable tray, and non-metallic trunking as the sole support of the cables in it. Note 4 gives suitably spaced steel or copper clips, saddles or ties as examples that comply, and Note 2 deems cables in or on steel containment to comply. The reason, in Note 1, is that wiring hanging across access or egress routes may hinder evacuation and firefighting.

Where to find it: BS 7671 Regulation 521.10.202 and Notes

Q30. A cable trunking run passes through a fire-resisting compartment wall. What sealing does Section 527 require, and when can internal sealing of the trunking be omitted?

Regulation 527.2.1 requires the openings left after the wiring system passes through the wall to be sealed to the degree of fire resistance the element had before it was penetrated. Regulation 527.2.2 adds that a conduit, ducting, trunking or busbar system penetrating an element with specified fire resistance must also be internally sealed. Internal sealing can be omitted under Regulation 527.2.3 where the system is classified as non-flame propagating, has a maximum internal cross-sectional area of 710 mm², and both the system and any termination in the compartments satisfy the BS EN 60529 test for IP33. Temporary sealing is needed during erection, and sealing disturbed during alterations must be reinstated as soon as practicable.

Where to find it: BS 7671 Regulations 527.2.1, 527.2.2, 527.2.3

Q31. A circuit supplies equipment containing electronic components, so the load current may contain DC components. Explain the RCD types in Regulation 531.3.3 and state when Type AC may be used.

Regulation 531.3.3 sets out four types. Type AC trips on alternating sinusoidal residual current only. Type A also trips on residual pulsating direct current. Type F does everything Type A does, plus composite residual currents and pulsating DC superimposed on smooth DC. Type B does everything Type F does and also trips on residual sinusoidal AC up to 1 kHz and on residual smooth direct current, independent of polarity. Type AC shall only be used to serve fixed equipment where it is known that the load current contains no DC components, for example simple heating or filament lighting with no electronics. So Type AC is not suitable here: select Type A, F or B to suit the residual currents the load can produce.

Where to find it: BS 7671 Regulation 531.3.3

Q32. Without using the adiabatic equation, what is the minimum copper protective conductor for a circuit with 25 mm² copper line conductors, and what minimum sizes apply to a protective conductor that is not part of a cable or wiring system enclosure?

16 mm². Regulation 543.1.4 allows Table 54.7 to be used where the size is not calculated by Regulation 543.1.3. For line conductors over 16 mm² and up to 35 mm², a protective conductor of the same material must be at least 16 mm²; for line conductors of 16 mm² or less it must be the same size as the line conductor. If the table gives a non-standard size, use the next larger standard size. Separately, Regulation 543.1.1 says a protective conductor that is not part of a cable, not formed by conduit, ducting or trunking and not inside a wiring system enclosure must be at least 2.5 mm² copper equivalent with mechanical protection, or 4 mm² without it.

Where to find it: BS 7671 Regulations 543.1.1, 543.1.4; Table 54.7

Q33. A dwelling has a PME supply with a 25 mm² copper PEN conductor. What is the minimum size of the main protective bonding conductor, and where should the bond to the incoming gas pipe be connected?

10 mm² copper. Regulation 544.1.1 says that where PME conditions apply, the main protective bonding conductor is selected according to the PEN conductor of the supply and Table 54.8. A PEN conductor of 35 mm² or less requires a minimum of 10 mm² copper equivalent, and the table note warns that the distributor's network conditions may require a larger conductor. Regulation 544.1.2 requires the connection as near as practicable to the point of entry, on the consumer's hard metal pipework before any branch, and where practicable within 600 mm of the meter outlet union. Without PME conditions the bond must be at least half the earthing conductor size, not less than 6 mm² and need not exceed 25 mm² copper.

Where to find it: BS 7671 Regulations 544.1.1, 544.1.2; Table 54.8

Q34. A battery energy storage system is installed in a house, and an RCD protects the AC supply circuit to its power conversion equipment (PCE). What type of RCD does Chapter 57 require, and what warning notices are needed?

Regulation 570.6.2.2 requires the RCD to be Type B, unless the PCE provides at least simple separation between its AC and DC sides, simple separation is provided by separate transformer windings, or the PCE manufacturer states that a Type B RCD is not required. Regulation 570.6.8.201 requires a notice showing the presence and location of the battery system at the origin, at each metering position if remote from the origin, and at each consumer unit or distribution board the battery supply connects to. Each battery room access or battery enclosure needs a permanent notice that live parts can remain energized after isolation, and all PCE must carry a notice to isolate both AC and DC sides before servicing (570.6.8.203).

Where to find it: BS 7671 Chapter 57: Regulations 570.6.2.2, 570.6.8.201 to 570.6.8.203

Q35. Which electrical sources for safety services are recognised by Chapter 56, and when may a separate feeder from the distributor's network be used as one?

Regulation 560.6.1 recognises four sources: primary batteries; stationary secondary batteries; other generating sets independent of the normal supply; and a separate feeder of the supply network that is effectively independent of the normal feeder. Regulation 560.6.5 says separated independent feeders from a distributor's network shall not serve as safety sources unless assurance can be obtained that the two supplies are unlikely to fail concurrently. The sources must also be installed as fixed equipment that cannot be adversely affected by failure of the normal source, be accessible only to skilled or instructed persons, and be ventilated so exhaust gases, smoke or fumes cannot reach occupied areas. Circuits of safety services must be independent of other circuits.

Where to find it: BS 7671 Regulations 560.6.1 to 560.6.5; 560.7.1

More practice on this Part, with a worked answer on every question

08 · 2382-26 Revision

Part 6: inspection and testing

Q36. During initial verification, which tests must be carried out before the installation is energized, in what order, and what must happen if a test shows a failure?

Regulation 643.1 requires the tests of Regulations 643.2 to 643.6, where relevant, to be carried out in that order before energizing: continuity of conductors, insulation resistance, protection by SELV, PELV or electrical separation, insulation resistance/impedance of floors and walls, and polarity. Where the installation has an earth electrode, the test of Regulation 643.7.2 is also done before energizing. If any test indicates a failure to comply, that test and any preceding test whose results may have been influenced by the fault must be repeated after the fault has been rectified. Instruments must be chosen in accordance with the relevant parts of BS EN 61557, or give no lesser performance and safety.

Where to find it: BS 7671 Regulation 643.1

Q37. What test voltage and minimum insulation resistance does Table 64 give for a 230 V circuit and for a SELV circuit, and how should a circuit be tested where connected equipment could be damaged by the test?

For a 230 V circuit (up to and including 500 V, other than SELV and PELV), Table 64 gives a test voltage of 500 V DC and a minimum of 1.0 MΩ. For SELV and PELV circuits the test voltage is 250 V DC and the minimum is 0.5 MΩ. Under Regulation 643.3.3, where connected equipment is likely to influence the result or be damaged, the test is applied before that equipment is connected. After connection, a test at 250 V DC is applied between live conductors and the protective conductor, and the reading must be at least 1 MΩ. Each distribution circuit is tested with its final circuits connected but current-using equipment disconnected.

Where to find it: BS 7671 Regulations 643.3.2, 643.3.3; Table 64

Q38. An electrician replaces the consumer unit in an existing house. What certificate must be issued, to whom, and how should defects in the new work and in the existing installation be dealt with?

An Electrical Installation Certificate. Regulation 644.1 requires one, based on the model in Appendix 6, on completion of a new installation or an addition or alteration, and it specifically includes the replacement of a distribution board or consumer unit. It is issued to the person ordering the work. Regulation 644.1.2 requires any defect or omission that will affect the safety of the addition or alteration to be corrected before the certificate is issued. Defects found in the existing installation are recorded on the certificate, so far as is reasonably practicable, by the person responsible for the new work.

Where to find it: BS 7671 Regulations 644.1, 644.1.2; Appendix 6

Q39. What must an Electrical Installation Condition Report include under Regulation 653.2, and what did Amendment 4 change in Regulations 653.1 and 653.2?

Regulation 653.2 requires: details of the parts inspected and tested; any limitations; any damage, deterioration, defects or dangerous conditions which might impair safety; any non-compliance with BS 7671 which might give rise to danger; schedules of inspection; schedules of circuit details and test results; and guidance for the recipient(s) based on the Appendix 6 model. Regulation 653.4 requires a recommended interval until the next inspection, supported by an explanation. The A4 introduction states that 653.1 now requires the Appendix 6 notes for the person producing the report to be taken into account, and 653.2 now requires the recipient guidance. A note adds that photographic and/or thermographic images can be attached to support observations.

Where to find it: BS 7671 Regulations 653.1, 653.2, 653.4; Introduction to Amendment 4:2026

More practice on this Part, with a worked answer on every question

09 · 2382-26 Revision

Part 7: special installations or locations

Q40. In a room containing a bath, what additional protection is required for low voltage circuits, how far does zone 2 extend, and how close to the bath may an ordinary 230 V socket-outlet be installed?

Regulation 701.411.3.3 requires additional protection by one or more RCDs with the characteristics of Regulation 415.1.1 for low voltage circuits serving the location, and for circuits passing through zones 1 and/or 2 that do not serve it. Zone 2 runs from the zone 1 boundary to a parallel vertical surface 0.60 m away, and up to the highest fixed shower head or water outlet or 2.25 m above finished floor level, whichever is higher. Under Regulation 701.512.3, socket-outlets, other than SELV socket-outlets and shaver supply units, are prohibited within 2.50 m horizontally of the zone 1 boundary.

Where to find it: BS 7671 Section 701: Regulations 701.411.3.3, 701.32.4, 701.512.3

Q41. On a construction site, how may a circuit supplying a 32 A socket-outlet be protected, and what applies to a circuit supplying a 63 A socket-outlet?

Regulation 704.410.3.10 requires a circuit supplying a socket-outlet rated up to and including 32 A, or hand-held equipment up to 32 A, to be protected by one of: reduced low voltage; automatic disconnection with additional protection by an RCD meeting Regulation 415.1.1; electrical separation, each socket-outlet or tool having its own transformer or winding; or SELV or PELV. Note 1 says reduced low voltage is strongly preferred for portable handlamps for general use, portable hand tools and local lighting up to 2 kW. For socket-outlet circuits rated above 32 A, such as 63 A, an RCD not exceeding 500 mA must be provided. A PME earthing facility shall not be used unless all extraneous-conductive-parts are reliably connected to the main earthing terminal.

Where to find it: BS 7671 Section 704: Regulations 704.410.3.10, 704.411.3.1, 704.411.3.2.1

Q42. What RCD protection does Section 705 require in agricultural and horticultural premises, and what restriction applies to PEN conductors there?

Regulation 705.411.1 requires, whatever the earthing system: an RCD with the characteristics of Regulation 415.1.1 on final circuits supplying socket-outlets rated not more than 32 A; an RCD not exceeding 100 mA on final circuits supplying socket-outlets rated more than 32 A; and RCDs not exceeding 300 mA on all other circuits. A PEN conductor shall not be used within the installation, including associated residences, though TN-C-S is not precluded. In locations intended for livestock, Regulation 705.415.2.1 requires supplementary bonding to connect all exposed-conductive-parts and extraneous-conductive-parts that can be touched by livestock, including any metal grid laid in the floor.

Where to find it: BS 7671 Section 705: Regulations 705.411.1, 705.411.4, 705.415.2.1

Q43. For a solar PV installation, which protective measures are permitted on the DC side, what degree of protection applies to enclosures installed outdoors, and where must PV presence notices be fixed?

Regulation 712.410.102 permits only double or reinforced insulation, or extra-low voltage by SELV or PELV, on the DC side. Regulation 712.410.101 says DC side equipment shall be considered energized even when the AC side is disconnected or the inverter is disconnected from the DC side. Under Regulation 712.512.102, outdoor enclosures need at least IP44 to BS EN 60529 and at least IK07 protection against external mechanical impact. Regulation 712.514.101 requires a notice showing a PV system is present at the origin, at the metering position if remote, and at the consumer unit or distribution board fed by the inverter. DC side access points need a notice that live parts can remain energized after isolation, and inverters need a warning to isolate both AC and DC sides before servicing.

Where to find it: BS 7671 Section 712: Regulations 712.410.102, 712.512.102, 712.514.101 to 712.514.103

Q44. Power over Ethernet is being used to supply luminaires through data cabling. What source voltages and current limits does Section 716 set, and where is a separate SELV or PELV source not allowed?

Section 716, introduced by A4, requires the protective measure SELV or PELV. The supply must come from power sourcing equipment to the referenced standards, or from a source to Regulation 414.3 not exceeding 60 V ripple-free DC in dry locations and 15 V ripple-free DC in all other locations. That second kind of source must not power ICT cabling that passes through, or serves, the special locations of Sections 701, 702, 703, 706 and 710. Regulation 716.523.2.101 limits the load (design) current in any conductor to 750 mA, and the connecting hardware must support a continuous 750 mA per contact.

Where to find it: BS 7671 Section 716: Regulations 716.410.3.3, 716.414.1.1, 716.414.3.201, 716.523.2.101, 716.526.101

Q45. An EV charging point that may charge a vehicle outdoors is to be installed on a PME supply. Under Regulation 722.411.4.1, what methods allow the PME earthing facility to be used for its protective conductor?

The PME earthing facility shall not be used unless one of indents (b) to (e) is applied; indent (a) has been deleted. (b) Connect the main earthing terminal to an earth electrode so that, with an open-circuit PEN fault, its voltage to Earth does not exceed 70 V RMS. (c) Fit a device that disconnects the vehicle from the live conductors and protective earth within 5 s if the cpc to Earth voltage exceeds 70 V RMS; it need not operate for less than 4 s. (d) Fit a device that disconnects within 5 s if the line to neutral voltage is greater than 253 V RMS or less than 207 V RMS. (e) Use an alternative device giving no lesser degree of safety.

Where to find it: BS 7671 Section 722: Regulation 722.411.4.1

Q46. An electric floor heating system is being installed under a tiled floor. What RCD and temperature requirements does Section 753 set?

Regulation 753.415.1 requires circuits supplying heating units to have additional protection by RCDs with the characteristics of Regulation 415.1.1, and time delayed type RCDs shall not be used. Where heating units arrive without exposed-conductive-parts, a conductive covering such as a metal grid with spacing of not more than 30 mm must be provided on site and connected to the protective conductor, unless suitable Class II units are used. For floor or ceiling systems, Regulation 753.424.201 requires measures to limit the temperature within the zone of the heating units to a maximum of 80 °C. Where skin or footwear can touch the floor, its surface temperature must be limited, for example to no more than 35 °C. Heating units shall not cross expansion joints.

Where to find it: BS 7671 Section 753: Regulations 753.411.3.2, 753.415.1, 753.423, 753.424.201, 753.515.101

More practice on this Part, with a worked answer on every question

10 · 2382-26 Revision

Part 8 and the appendices

Q47. What does Part 8 of BS 7671:2018+A4:2026 contain, and where would you look for the former Appendix 17 on energy efficiency?

Part 8 has two chapters. Chapter 81, Functional aspects: energy efficiency, is informative. It points to Building Regulations guidance for England, Wales, Scotland and Northern Ireland, such as Approved Document L, and to BS HD 60364-8-1:2019. Chapter 82, Prosumer's low voltage electrical installations, provides additional requirements, measures and recommendations for design, erection and verification of installations with local production and/or storage of energy, called prosumer's electrical installations (PEIs), so they operate safely and efficiently within smart grids. It does not cover sources for safety services. Appendix 17 has been deleted by A4 and replaced by Chapter 81, so energy efficiency is now found in Part 8.

Where to find it: BS 7671 Part 8, Chapters 81 and 82; Introduction to Amendment 4:2026

Q48. Chapter 82 describes types and operating modes of prosumer's electrical installations (PEIs). Name them, and state the isolation requirement where an installation is supplied from more than one source.

Regulation 824.1 lists three types of PEI: individual, collective and shared. Regulation 824.2 gives the main operating modes for each type: direct feeding mode, reverse feeding mode and island mode. Transfer between direct feeding and island mode is made by the switching device for islanding, which must comply with Regulation 512.1.2 and its product standard and be suitable for isolation. Where an installation has more than one source, Regulation 826.1.1.4 requires a main switch suitable for isolation for each source, with a durable warning notice nearby telling anyone to operate all such switches to isolate the installation, or a suitable interlock. An electrical energy management system (EEMS) monitors and controls the supplies, storage and loads.

Where to find it: BS 7671 Chapter 82: Regulations 824.1, 824.2, 825.1, 826.1.1.4, 826.1.1.5

Q49. The time/current curves in Appendix 3 show that a 16 A Type B circuit-breaker to BS EN 60898 operates within 0.4 s at 80 A. Calculate the maximum earth fault loop impedance for a 230 V circuit, and the maximum value you could accept when measuring at ambient temperature.

The maximum Zs is 2.73 Ω and the maximum measured value is about 2.18 Ω.

  1. Step 1: Appendix 3 gives Zs = Uo × Cmin ÷ Ia, with Cmin given the value 0.95 for a supply under the ESQCR.
  2. Step 2: Zs = 230 × 0.95 ÷ 80 = 218.5 ÷ 80 = 2.73 Ω, which matches the Type B 16 A value in Table 41.3.
  3. Step 3: Appendix 3 applies a factor of 0.8 to allow for conductor resistance rising with temperature under load, so the measured limit is 0.8 × 2.73 = 2.18 Ω.

Conclusion: a measured Zs at or below about 2.18 Ω is considered to meet Regulation 411.4.4, unless the manufacturer's data gives a different limit.

Where to find it: BS 7671 Appendix 3; Table 41.3

Q50. Using the Appendix 6 model forms, explain the classification codes used on an Electrical Installation Condition Report, which of them make the overall assessment unsatisfactory, and what A4 changed about code FI.

C1 means danger present, C2 potentially dangerous, C3 improvement recommended, and FI further investigation advised. The Appendix 6 notes for the person producing the report say the overall assessment is to be reported as unsatisfactory where any observation is coded C1 or C2. The model report form adds that C1 and C2 items should be acted on as a matter of urgency. C3 and FI are advisory and do not affect the overall assessment. FI is used where the inspector has identified an issue they cannot verify because of the extent and limitations. Wherever practicable, C1 items are made safe on discovery. The A4 introduction confirms the code FI no longer needs to be marked as unsatisfactory.

Where to find it: BS 7671 Appendix 6, Condition Report notes and Section K; Introduction to Amendment 4:2026

More practice on this Part, with a worked answer on every question

Frequently Asked Questions

What electricians say

Verified reviews from the UK App Store.

One App for Everything!

Elec-Mate is my go to app for business and electrical work. It's feature rich without feeling cluttered. A true all in one app for quotes, certs, calculations, RAMS, EICRs, and more. I use it every day without fail, and it makes my workflow much smoother since I'm not jumping between apps anymore. The price-to-feature ratio is excellent. Any issues I've had, the developer responds within the hour and usually fixes them the same day. 100% recommend.

Apple App Store · GBR

Fantastic app for electricians

I've used the app and the web based version for a while now and it's well worth the investment. If you're an apprentice or experienced Spark give it a go, you won't be disappointed.

Apple App Store · GBR

Absolutely amazing

I've been using Elec-Mate for a while now, and honestly, it's one of the best apps I've ever downloaded. Every aspect of it feels thoughtfully designed, from the clean and intuitive interface to the powerful features that make everything so easy to manage. It's clear that a lot of care and attention went into building this app, and it shows in every detail.

Apple App Store · GBR

Trusted by electricians across the UK

Real feedback from electricians and apprentices

“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”

Daniel Palmer

Sole Trader · DP Electrical

“I've won two contracts this month because I could turn quotes around same-day with the AI cost engineer.”

Nathan Perry

Electrician · NP Electrical Services

“The study centre got me through my AM2. Mock exams and flashcards are brilliant.”

Jake Pizey

3rd Year Apprentice · Apprentice

7 days free

Revise all of BS 7671 in one place

The Study Centre has the full 18th Edition course, 60+ mock exams and 20,000+ practice questions. Try it free for 7 days. £0 today, card required.

Start your free week

£0 today, then from £6.99/mo after your free week.

“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”

Daniel Palmer, DP Electrical · 5 out of 5
  • 7 days free, then from £6.99/mo
  • Cancel in two taps, no phone calls
  • iOS, Android and web
  • Built to BS 7671:2018+A4:2026

Or download the app

Download on the App StoreGet it on Google Play