The device plugs into a fixed socket-outlet complying with BS 1363-2, and it must not be connected to damaged, degraded or non-compliant socket-outlets. Where the inverter and the socket are both mounted outside, the socket needs an ingress protection rating of IP55 or better.
That combination — panels outside, sockets usually inside, and no extension leads permitted — is why a fixed outdoor socket-outlet is so often the first real piece of electrical work a plug-in solar installation creates.
Only one device is permitted per circuit, so somebody has to be able to identify which sockets share one. Where the consumer unit does not use modern protective devices, is not clearly labelled, or is of unknown condition, the specification says users should seek inspection and assessment by a qualified electrician before installing the product.
Ring final circuits are fine. A small number of consultation respondents argued otherwise, and the government’s published safety study tested plug-in solar in representative UK installations including ring circuits, finding nothing that would prevent safe operation at 800 W on appropriately protected rings.